Laserfiche WebLink
20.24.130 <br /> <br />20.24.140 <br /> <br />feet, with a maximum coverage of 100 square feet per <br />sprinkler is required. A 500 gallon per minute allowance <br />for hose streams shall also be provided. <br /> <br />Where the underside of roof sheathing is twenty four (24') <br />feet or more to the finished floor, a sprinkler design of .60 <br />gallons per minute calculated over the hydraulically most <br />remote 3,000 square feet, with a minimum sprinkler <br />spacing of eight by eight feet (8' X 8'). A 500 gallon per <br />minute allowance for hose streams shall also be provided. <br /> <br />Where fire service booster and/or fire pumps are required to <br />meet fire protection requirements, a minimum of two (2) <br />fire service booster and/or fire pumps is required. Each fire <br />pump shall be powered by a diesel engine. <br /> <br />UFC Section 1003.1.2.2 added--Installation of Fire Sprinkler <br /> <br />Systems. <br /> <br />Section 1003.1.2.2 is added to the Uniform Fire Code to read: <br /> <br />Section 1003.1.2.2 <br /> <br />A minimum design area of 3,000 square feet shall be <br />required for all industrial/commercial sprinkler systems. <br />Where subsequent occupancy requires a sprinkler system <br />of greater design density or area of application capability, it <br />shall be the responsibility of the owner and/or occupant to <br />retrofit the sprinkler system to the required code or <br />standard in order to obtain clearance for the new occupancy <br />or use. <br /> <br />UFC Section 1003.1.2.3 added--Installation of Fire Sprinkler <br /> <br /> Systems. <br /> <br />Section 1003.1.2.3 is added to the Uniform Fire Code to read: <br />Section 1003.1.2.3 <br /> <br />Fire sprinkler protection shall be provided in all combustible and <br />non-combustible concealed spaces. <br /> <br />20.24.150 <br /> <br />UFC Section 1003.3.1, Where required amended. <br /> 103 <br /> <br /> <br />