Laserfiche WebLink
Attachment 1 Exhibit B <br />Page 28 of 64 <br /> <br />20.24.130 CFC Chapter 2 Definitions added – Maximum Threshold Quantity <br /> <br />The definition of Maximum Threshold Quantity is added as follows: <br /> <br />MAXIMUM THRESHOLD QUANTITY. The following formula shall be used to calculate the maximum <br />threshold quantity for toxic, highly toxic, and moderately toxic gases: <br /> <br /> Max TQ (lbs.) = LC50 (ppm) x 2 lb. <br /> <br />For gas mixtures containing one or more toxic, highly toxic or moderately toxic components, the LC50 <br />shall be calculated using CGA Standards P-20 and P-23. <br /> <br />20.24.140 CFC Chapter 2 Definitions added – Moderately Toxic Gas <br /> <br />The definition of Moderately Toxic Gas is added as follows: <br /> <br />MODERATELY TOXIC GAS. A chemical or substance that has a medial lethal concentration <br />(LC50) in air of more than 2,000 parts per million but not more than 5,000 parts per million by volume <br />of gas or vapor, when administered by continuous inhalation for an hour, or less if death occurs within <br />one hour, to albino rats weighing between 200 and 300 grams each. <br /> <br />20.24.145 CFC Chapter 6, Section 603.10 added- Multiple sources of non-utility electricity <br /> <br />Section 603.10 is added to read: <br /> <br />603.10 Multiple sources of non-utility electricity. When a facility has more than one source of non- <br />utility-based electrical utility power, including emergency and standby power systems, a written <br />shutdown plan shall be provided. A copy of the plan will be posted at or near the main electrical panel <br />in a location approved by the Fire Department. A copy of the plan will be provided in a format <br />acceptable to the Fire Department. <br /> <br />20.24.150 CFC Section 611 added – Immersion Heaters. <br /> <br />Section 611 is added to read: <br /> <br />611.1Immersion Heaters. All electrical immersion heaters used in dip tanks, sinks, vats and similar <br />operations shall be provided with approved over-temperature controls and low liquid level electrical <br />disconnects. Manual reset of required protection devices shall be provided. <br /> <br />CFC Section 901.6.4 added – Prevention of False Alarms <br /> <br />901.6.4 is added to read: <br /> <br />901.6.4 Prevention of False Alarms. <br />1. It is unlawful for any property owner or licensed contractor to fail to notify the police/fire <br />department dispatch center prior to any test, installation, repair, modification, addition, or <br />maintenance of any fire alarm or fire extinguishing system which could result in the transmission <br />of an unwanted alarm. <br />Page 39 of 376