Attachment 1 Exhibit B <br />Page 36 of 64 <br />6004.1.10 Exhaust ventilation monitoring. For highly toxic gases, toxic and moderately toxic gases <br />exceeding minimum threshold quantities, a continuous monitoring system shall be provided to assure <br />that the required exhaust ventilation rate is maintained. The system shall monitor actual air flow in the <br />exhaust system. The monitoring system shall initiate a local alarm. The alarm shall be both visual <br />and audible and shall be designed to provide warning both inside and outside of the interior storage, <br />use, or handling area. <br /> <br />20.24.390 CFC Section 6004.1.11 added – Emergency response plan. <br /> <br />Section 6004.1.11 is added to read: <br /> <br />6004.1.11 Emergency response plan. If the preparation of an emergency response plan for the <br />facility is not required by any other law, responsible persons shall prepare, or cause to be prepared, <br />and filed with the fire code official, a written emergency response plan. If the preparation of an <br />emergency response plan is required by other law, a responsible person shall file a copy of the plan <br />with the fire code official. <br /> <br />20.24.400 CFC Section 6004.1.12 added – Emergency Response Liaisons. <br /> <br />Section 6004.1.12 is added to read: <br /> <br />6004.1.12 Emergency Response Liaisons. Responsible persons shall be designated and trained to be <br />liaison personnel for the Livermore-Pleasanton Fire Department. There persons shall aid the Fire <br />Department in preplanning emergency responses and understanding the materials and operations <br />utilizing the gases. <br /> <br />20.24.410 CFC Section 6004.1.13 added – Emergency Drills. <br /> <br />Section 6004.1.13 is added to read: <br /> <br />6004.1.13 Emergency Drills. Emergency drills of the on-site emergency response personnel and <br />liaisons shall be conducted on a regular basis but not less than every six months. Records of drills <br />conducted shall be maintained for three years. <br /> <br />20.24.420 CFC Section 6004.1.14 added – Cylinder leak testing. <br /> <br />Section 6004.1.14 is added to read: <br /> <br />6004.1.14 Cylinder leak testing. Cylinders shall be tested for leaks immediately upon delivery and <br />again immediately prior to departure. Testing shall be approved by the fire code official in accordance <br />with appropriate nationally recognized industry standards and practices, if any. Appropriate remedial <br />action shall be immediately undertaken when leaks are detected. <br /> <br />20.24.430 CFC Section 6004.1.15 added – Inert gas purge system. <br /> <br />Section 6004.1.15 is added to read: <br /> <br />6004.1.15 Inert gas purge system. Gas systems shall be provided with dedicated inert gas purge <br />systems. A dedicated inert gas purge system may be used to purge more than one gas, provided the <br />gases are compatible. Purge gas systems inside buildings shall be located in an approved gas cabinet <br />unless the system operates by vacuum demand. <br />Page 47 of 376