PC-2026-16 June 24, 2026 <br /> <br />Minimum number of fire hydrants (subject to approval by Livermore-Pleasanton <br />Fire Department (LPFD) Fire Marshal: 1 hydrant within 250 feet of any existing or <br />proposed structure <br />Minimum pipe size: 8-inch diameter <br />Minimum depth of cover over pipe: 42 inches <br />Blowoff requirements: <br /> At all dead ends whether temporary or permanent <br /> At all low points in the line <br />Minimum fire flows in gallons per minute (gpm): 2,000 to 2,500 gpm for 2 hours <br />(single family residential) <br />Minimum pressures: <br />40 psi (peak hour demand) <br /> 20 psi (maximum day demand plus fire flows) <br />Dwelling unit equivalent flows: 160 gallons per day (single family residential) <br /> <br />78. BACKFLOW PREVENTION ASSEMBLIES: Backflow preventer assemblies shall <br />be designed and installed in accordance with current City Standard Drawings <br />704, 705, 706; Pleasanton Municipal Code Chapter 14.16, State Health and <br />Safety Code; State Water Resources Control Board adopted Cross-Connection <br />Control Policy Handbook (CCCPH); and as required by the Public Works <br />Department. Backflow Preventers (BFP) shall be selected from the latest “List of <br />Approved Backflow Prevention Assemblies” available from the Foundation for <br />Cross-Connection Control and Hydraulic Research at the University of Southern <br />California. All backflow preventer assemblies shall be tested and certified by a <br />City approved tester with the certification submitted to the City. Testing will be <br />performed at the time City water is turned on to the site. If an existing backflow <br />preventer is on the site, it shall be tested and certified by a City-approved tester <br />with the certification submitted to the City before project water is drawn through <br />it. An all-weather cover shall be placed over all backflow prevention assemblies <br />4 inches and smaller, and follow City Standard Specification 19-02N for backflow <br />enclosure requirements. (Fulfill this condition prior to plan approval.) <br /> <br />79. SINGLE-FAMILY RESIDENTIAL FIRE PROTECTION SYSTEMS AND <br />BACKFLOW PREVENTION: Single-family residential water services which <br />include a fire protection system must be equipped with either Double Check (DC) <br />valve backflow protection (requiring annual testing) or satisfy CCCPH section <br />3.2.2(e)(3) with pass-through/purge design of fire protection system with signage <br />posted at fixture to bring attention to the system design with pass-through/purge. <br />If applicant selects to install DC, assembly shall be designed and installed in <br />accordance with current City Standards 704, 705, and PMC 14.16; including <br />installation as close as possible to the service line before the first branch line <br />leading off the service line. (Fulfill this condition prior to plan approval.) <br /> <br />        <br /><br /><br /><br />