20.20.027 <br />cuit is matched to the voltage rating <br />and charge current requirements of <br />the interconnected battery cells and <br />the maximum charging current multi- <br />plied by 1 hour is less than 3 percent <br />of the rated battery capacity ex- <br />pressed in ampere-hours or as recom- <br />mended by the battery manufacturer. <br />All adjusting means for control of <br />the charging process shall be accessi- <br />ble only to qualified persons. <br />(3) Circuits Using Inverters. The <br />requirements in 690.72(B)(2) shall <br />not apply to ac or do circuits using <br />inverters to control the battery <br />charging process by feeding power <br />into the utility system. These cir- <br />cuits, used in several modes, shall <br />be sized and protected as required <br />in 690.8. <br />690.74 Battery Interconnections. <br />FPN: Certain battery types such as Flexible cables, as identified in Arti- <br />valve-regulated lead acid or nickel cle 400, in sizes 2/0 AWG and larger <br />cadmium can experience thermal shall be permitted within the battery <br />failure when overcharged. enclosure from battery terminals to a <br /> nearby junction box where they shall <br />(B) Diversion Charge Controller. be connected to an approved wiring <br /> method. Flexible battery cables shall <br />(1) Sole Means of Regulating Charg- also be permitted between batteries <br />ing. A photovoltaic power system and cells within the battery enclo- <br />employing a diversion charge con- sure. Such cables shall be listed for <br />troller as the sole means of regulat- hard service use and identified as <br />ing the charging of a battery shall be moisture resistant. <br />equipped with a second independent <br />means to prevent overcharging of the IX. Systems Over 600 Volts <br />battery. <br /> 690.80 General. <br />(2) Circuits with Direct Current Di- <br />version Charge Controller and Diver- Solar photovoltaic systems with a <br />sion Load. Circuits containing a do maximum system voltage over 600 <br />diversion charge controller and a do volts do shall comply with Article <br />diversion load shall comply with the 490 and other requirements applica- <br />following: ble to installations rated over 600 <br /> volts. <br />(1) The current rating of the diver- <br />sion load shall be rated at least 150 <br />percent of the current rating of the <br />diversion charge controller. <br />(2) The conductor ampacity and the <br />rating of the over current device <br />for this circuit shall be at least 150 <br />percent of the maximum current <br />rating of the diversion charge con- <br />troller. <br />690.85 Definitions. <br />For the purposes of Part IX of this <br />article, the voltages used to deter- <br />mine cable and equipment ratings are <br />as follows. <br />Battery Circuits. In battery circuits, <br />the highest voltage experienced un- <br />710-31 (Pleasanton April 2003) <br />