[ii] Valves shall be permanently marked to indicate the maximum design flow rate. <br /> <br />(5) Gas Detection. A continuous gas-detection system (in accordance with the Uniform <br />Fire Code, Section 8003.3.1.6) shall be provided to detect the presence of gas at or below <br />the permissible exposure limit. The detection system shall initiate a local alarm and <br />transmit a signal to an approved Undem~riters Laboratory (UL) Central Station Service as <br />directed by the Fire Chief, to provide an immediate response to an alarm. The alarm shall <br />be both visual and audible and shall be designed to provide warning both inside and <br />outside of the storage, use or handling area. The audible alarm shall be distinct from all <br />other on-site alarms. <br /> <br />(6) Reduced Flow Valves. Reduced flow valves may be utilized to reduce the maximum <br />flow rate from cylinders and tanks under full flow conditions. Valve flow rates may be <br />considered in determining the size of treatment systems required for a worst case release. <br /> <br />(7) Seismic Shut-offValves. A seismologically activated valve meeting standards <br />approved by the Fire Chief shall be provided for automatic shut off of regulated materials <br />upon a seismic event within 5 seconds of horizontal semisoidal oscillation having a peak <br />acceleration of. 15g (=1.47m/sec2) and a period of .4 seconds. <br /> <br />(8) Class II Corrosives. Inert construction materials shall be used for the primary <br />containment of Class II Regulated Materials which are corrosives. Alternatively, <br />secondary containment shall be provided for Class II materials which are corrosives. <br /> <br />(9) Emergency Alarms. When materials regulated by this Article are transported through <br />exit corridors or exit enclosures, there shall be an emergency telephone system or a local <br />manual alarm station or a signaling device approved by the Fire Chief at not more than <br />150-foot intervals and at each exit doorway throughout the transport route. The signal <br />shall be relayed to an approved Underwriters Laboratory (UL) Central Station Service as <br />directed by the Fire Chief and shall also initiate a local audible alarm. <br /> <br />(d) Class III Controls. <br /> <br />Persons responsible for a facility shall cause materials which are classified as Class III <br />materials to be provided with the controls specified in this subsection (d) and in <br />subsections (e) and (f) of this section. <br /> <br />(1) Piping, valves and fittings. <br /> <br />[i] Piping, valves, fittings and related components shall be designed and fabricated from <br />materials compatible with the material to be contained. They shall have strength and <br />durability sufficient to withstand the pressure, structural and seismic, and any other stress <br />and exposure to which they may be subjected. <br /> 121 <br /> <br /> <br />