Laserfiche WebLink
Objectjye pesjgn standards toe Multitaroilv Hoysjng in B-M, c-c, and M-U Zonjng Pistrjcts <br />B8. Site Lighting <br />Site lighting should enhance security , contribute to attractive site design, and make efficient use of <br />energy. <br />Development Standards <br />All Sites <br />B8.1 All exterior site area lighting shall comply with the following standards : <br />a. Specified Site Lighting fixtures shall demonstrate a m aximum Backlight Up light Glare <br />(BUG) rating of 83 U0 G 1, unless California Building Code req uirements for the fixture <br />location are more stringent. <br />b. All site area lighting shall be appropriate fo r California Energy Commission Lighting Zo ne 3 , <br />as defined by California building code. <br />c. Light trespas s across property lines shall be limited to 0 .1 footcandles. <br />B8.2 Proposed LED luminaries shall be demonstrated through manufacturer 's data to comply with <br />California Energy Commission Reference Appendix JA-8; or the following: <br />a. Maintain color temperature of2700-3000k; <br />b . Provide a minimum Color Rendering Index of90 ; <br />c. Provide R9 value of 50 or higher; and <br />d . The L70 life expectancy of the illumination source shall exceed 25,000 hours . <br />B8.3 Area lighting used for parking areas , service areas, access drives, and internal vehicular <br />circulation shall comply with the following standards: <br />a. Area lighting fixture mounting height shall not exceed 25 feet from adjacent ground. <br />b . Service area illumination shall be entirely contained with in the limits of the service area. <br />City of Pleasanton -23 -January 5, 2023 -DRAFT