LIGHTING PLAN <br />GENERAL NOTES: <br />DAYLIGHT CONTROL EXCEPTION NOTES: <br />DAYLIGHT CONTROL: COMBINED TOTAL GENERAL LIGHTING POWER IN <br />PRIMARY/SECONDARY SIDELIT DAYLIT ZONE IS LESS THAN 120 WATTS. NO <br />DAYLIGHT CONTROL REQUIRED. [2022 CENC130.1(D)EXCEPTION(3)] <br />1.EMERGENCY/NL AND EXIT FIXTURES TO BE CONNECTED TO NEARBY ROOM <br />LIGHTING CIRCUIT AHEAD OF LOCAL SWITCH. IF EXISTING, VERIFY <br />CONDITION AND RE-USE. [CEC 700.12(I)(2)(3)(A)] <br />2.INTERLOCK RESTROOM LIGHT WITH EXHAUST FAN AND PROVIDE MANUAL <br />MOTOR SWITCH IF NOT PLUG/BUILT-IN. <br />3.ALL EXISTING LIGHTING/CONTROL FIXTURES IN THIS AREA TO REMAIN U.O.N. <br />NOT IN SCOPE. <br />#KEYED LIGHTING PLAN NOTES: <br />(E) <br />1 <br />(E) <br />(E) <br />1 <br />(E)(E) <br />(E) <br />(E) <br />(E)(E) <br />(E)(E)(E)(E) <br />(E)(E)(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E)(E) <br />(E)(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E <br />) <br />(E <br />) <br />(E <br />) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />R <br />(E) <br />R <br />(E) <br />R <br />(E) <br />(E <br />) <br />(E) <br />(E) <br />(E)(E) <br />R <br />(E) <br />R <br />(E) <br />R <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E) <br />(E)(E) <br />(E) <br />(E) <br />R <br />(E) <br />1 <br />1 (E) <br />1 <br />(E) <br />D/OS <br />1.ELECTRICAL EQUIPMENT SHALL BE LISTED BY U.L. OR CITY RECOGNIZED <br />ELECTRICAL TESTING LABORATORY OR APPROVED BY THE CITY <br />DEPARTMENT. <br />2.ALL ELECTRICAL WORK SHALL COMPLY WITH THE [2022 CEC]. <br />3.WIRE SIZE SHALL NOT BE LESS THAN CORRESPONDING CIRCUIT BREAKER <br />RATING AS REQUIRED. [2022 CEC TABLE 310.16] <br />4.CONDUIT SHALL BE SIZED IN ACCORDANCE WITH THE [2022 CEC ANNEX C]. <br />5.CONTRACTOR/ELECTRICIAN TO FIELD VERIFY ACTUAL SITE CONDITION <br />/EXACT SERVICE ENTRANCE AND SHALL NOTIFY EOR(S) ANY DISCREPANCY <br />WITH THE PLAN PRIOR TO BIDDING. <br />6.ALL ITEMS LABELED/IDENTIFIED AS EXISTING (IF ANY) ARE SUBJECT TO <br />FIELD VERIFICATION. VERIFY EXISTING CONDITION AND RE-USE. IF NOT <br />EXISTING, PROVIDE PER PLAN. <br />7.OBTAIN APPROVAL ON LOCATION OF SWITCH/DIMMER/SENSOR WITH <br />ARCHITECT/OWNER AT SITE PRIOR TO ROUGH-IN. <br />8.SIGNAGE WILL REQUIRE SEPARATE PERMIT AND SUBMITTAL. <br />9.REFER TO EMERGENCY EXIT ILLUMINATION NOTES FOR EMERGENCY <br />LIGHTING REQUIREMENTS. <br />10.IN OFFICES 250 SQUARE FEET OR SMALLER, MULTIPURPOSE ROOMS OF <br />LESS THAN 1,000 SQUARE FEET, CLASSROOMS OF ANY SIZE, CONFERENCE <br />ROOMS OF ANY SIZE, AND RESTROOMS OF ANY SIZE, LIGHTING SHALL BE <br />CONTROLLED WITH OCCUPANT SENSING CONTROLS TO AUTOMATICALLY <br />SHUT OFF ALL OF THE LIGHTING IN 20 MINUTES OR LESS AFTER THE <br />CONTROL ZONE IS UNOCCUPIED. [2022 CENC 130.1(C)(5)] <br />A.IN AREAS W/ MULTI-LEVEL LIGHTING CONTROLS, THE OCCUPANT <br />SENSING CONTROLS SHALL FUNCTION AS A PARTIAL-ON OCCUPANT <br />SENSING CONTROLS CAPABLE OF AUTOMATICALLY ACTIVATING <br />BETWEEN 50 AND 70 PERCENT OF CONTROLLED LIGHTING POWER <br />B.IN AREAS W/O MULTILEVEL LIGHTING CONTROLS, THE OCCUPANT <br />SENSING CONTROLS SHALL FUNCTION AS A VACANCY SENSING <br />CONTROLS, WHERE ALL LIGHTING RESPONDS TO A MANUAL ON INPUT <br />ONLY. <br />11.IN OFFICE SPACES GREATER THAN 250 SQUARE FEET, GENERAL LIGHTING <br />SHALL BE CONTROLLED WITH OCCUPANT SENSING CONTROLS THAT MEET <br />ALL OF THE FOLLOWING: [2022 CENC 130.1(C)(6)(D)] <br />A.THE OCCUPANT SENSING CONTROLS SHALL BE CONFIGURED SO THAT <br />LIGHTING SHALL BE CONTROLLED SEPARATELY IN CONTROL ZONES NOT <br />GREATER THAN 600 SQUARE FEET. FOR LUMINAIRES WITH AN <br />EMBEDDED OCCUPANT SENSOR THAT ARE CAPABLE OF REDUCING <br />POWER INDEPENDENTLY FROM OTHER LUMINAIRES, EACH LUMINAIRE <br />CAN BE CONSIDERED ITS OWN CONTROL ZONE; AND <br />B.IN 20 MINUTES OR LESS AFTER THE CONTROL ZONE IS UNOCCUPIED, <br />THE OCCUPANT SENSING CONTROLS SHALL UNIFORMLY REDUCE <br />LIGHTING POWER IN THE CONTROL ZONE TO BY AT LEAST 80 PERCENT <br />OF FULL POWER. CONTROL FUNCTIONS THAT SWITCH CONTROL ZONE <br />LIGHTS COMPLETELY OFF WHEN THE ZONE IS VACANT MEET THIS <br />REQUIREMENT; AND <br />C.IN 20 MINUTES OR LESS AFTER THE ENTIRE OFFICE SPACE IS <br />UNOCCUPIED, THE OCCUPANT SENSING CONTROLS SHALL <br />AUTOMATICALLY TURN OFF LIGHTING IN ALL CONTROL ZONES IN THE <br />SPACE; AND <br />D.IN EACH CONTROL ZONE, LIGHTING SHALL BE ALLOWED TO <br />AUTOMATICALLY TURN ON TO ANY LEVEL UP TO FULL POWER UPON <br />OCCUPANCY WITHIN THE CONTROL ZONE. WHEN OCCUPANCY IS <br />DETECTED IN ANY CONTROL ZONE IN THE SPACE, THE LIGHTING IN <br />OTHER CONTROL ZONES THAT ARE UNOCCUPIED SHALL OPERATE AT NO <br />MORE THAN 20 PERCENT OF FULL POWER. <br />EE <br />EE <br />EE <br />EE EE <br />EE <br />EE <br />EE <br />EE <br />EE <br />EE <br />EE <br />EE <br />EE <br />EEEE <br />EE <br />EE <br />EE <br />EE <br />TO EXISTING CKTS <br />3 <br />3 <br />3 <br />3 <br />3 <br />3 <br />3 3 <br />3 <br />D/OS <br />TO EXISTING CKTS <br />D/OS <br />TO EXISTING CKTS <br />(N) DAYCARE 5 <br />(E) BREAK RM <br />(E) MEN'S <br />RESTROOM <br />(E) WOMEN'S <br />RESTROOM <br />(E) OFFICE 1 (E) LOBBY/ <br />RECEPTION <br />(N) DAYCARE 1 <br />(E) HALLWAY D <br />(E) OFFICE 2 <br />(N) DAYCARE 4(E) OFFICE 3 <br />FIRE SPRINKLER <br />RM <br />ELECTRICAL RM <br />(E) RESTROOM LOBBY <br />(E) STORAGE <br />(N) DAYCARE 6 <br />(E) STAFF <br />HALLWAY E <br />(E) JANITORIAL <br />100 <br />101 <br />120 <br />118 <br />117 <br />116 <br />110 <br />109 <br />125 <br />111 <br />112 <br />107 106 <br />105 <br />124 <br />(E) DAYCARE 2 <br />(N) DAYCARE 3 <br />104 <br />103 <br />102 <br />(N) LIBRARY <br />STACK AREA <br />128 <br />108 <br />119 <br />(N) HALLWAY B <br />122 <br />121 <br />123 <br />(E) STAFF <br />ALLEY <br />126 <br />(E) BOY'S <br />RESTROOM <br />(E) GIRL'S <br />RESTROOM <br />114 <br />(N) PLAY AREA <br />(N) LIBRARY <br />READING AREA <br />127 <br />129 <br />(E) HALLWAY A <br />(E) HALLWAY C <br />115 <br />(E) STUDENT <br />HANDWASH <br />AREA <br />D/OS <br />TO EXISTING CKTS <br />D/OS <br />TO EXISTING CKTS <br />D/OS <br />TO EXISTING CKTS <br />(E) <br />RE <br />V <br />I <br />S <br />I <br />O <br />N <br />SHEET TITLE: <br />DATE: SCALE: <br />11/14/2023 <br />PLOT DATE: 5/13/2024 12:05:03 PM <br />CD <br />I <br /> <br />Ci <br />r <br />c <br />a <br /> <br />D <br />o <br />m <br />i <br />n <br />i <br /> <br />I <br />n <br />t <br />e <br />r <br />n <br />a <br />t <br />i <br />o <br />n <br />a <br />l <br />, <br /> <br />I <br />n <br />c <br />. <br />En <br />g <br />i <br />n <br />e <br />e <br />r <br />i <br />n <br />g <br /> <br />- <br /> <br />C <br />o <br />n <br />s <br />u <br />l <br />t <br />i <br />n <br />g <br />98 <br />9 <br />0 <br /> <br />R <br />e <br />s <br />e <br />a <br />r <br />c <br />h <br /> <br />D <br />r <br />. <br /> <br />S <br />u <br />i <br />t <br />e <br /> <br />1 <br />0 <br />0 <br />, <br /> <br />I <br />r <br />v <br />i <br />n <br />e <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />6 <br />1 <br />8 <br />Ph <br />o <br />n <br />e <br /> <br />( <br />9 <br />4 <br />9 <br />) <br /> <br />5 <br />3 <br />3 <br />- <br />4 <br />1 <br />1 <br />7 <br /> <br />| <br /> <br />d <br />k <br />a <br />n <br />g <br />@ <br />c <br />d <br />i <br />e <br />n <br />g <br />. <br />c <br />o <br />m <br />66 <br />6 <br />3 <br /> <br />O <br />W <br />E <br />N <br />S <br /> <br />D <br />R <br />, <br />PL <br />E <br />A <br />S <br />A <br />N <br />T <br />O <br />N <br />, <br /> <br />C <br />A <br /> <br />9 <br />4 <br />5 <br />8 <br />8 <br />DRAWN: CHECKED: <br />AC <br />A <br />D <br />E <br />M <br />I <br />C <br /> <br />C <br />E <br />N <br />T <br />E <br />R <br />VO <br />L <br />I <br />T <br />A <br />T <br />I <br />O <br />N <br /> <br />C <br />O <br />R <br />P <br />. <br /> <br />D <br />A <br />Y <br />C <br />A <br />R <br />E <br />E100 <br />1/8" = 1'-0" <br />LIGHTING PLAN <br />J.L.K.T