Laserfiche WebLink
20.24.120 <br />(1) Piping. [iii] Failure of emergency <br />power. <br />[i] Piping for Class I mate- <br />rials shall be designed and fab- [iv] Seismic activity, upon <br />ricated from materials compati- a seismic event within 5 sec- <br />ble with the material to be con- onds of horizontal semisoidal <br />tained. Piping shall be of oscillation having a peak accel- <br />strength and durability sufficient eration of .15g (=1.47m/sec2) <br />to withstand the pressure, struc- and a period of .4 seconds. <br />tural and seismic stress and <br />exposure to which it may be [v] Failure of primary <br />subjected, as required by the containment. <br />Uniform Building Code or the <br />Pleasanton Municipal Code. [vi] Activation of manual <br />fire alarm. <br />[ii] Secondary containment <br />shall be provided for piping for [vii] Activation of an auto- <br />Class Imaterials. The secondary matic fire suppression system. <br />containment shall be capable of <br />directing a sudden release into (3) Emergency Control Station. <br />an approved discharge treatment Signals from emergency equip- <br />system, and shall be monitored ment shall be transmitted to an <br />continually with a continuous emergency control station which is <br />gas monitoring system approved continually staffed by trained <br />by the Fire Chief. Secondary personnel, and transmitted to an <br />containment, includes, but is not approved central station. <br />limited to, double walled pip- <br />ing. (c) Class II Controls. Responsible <br /> persons shall cause materials which <br />(2) Automatic Shut-Off. An are classified as Class II materials to <br />automatic shut-off valve which is be provided with the controls speci- <br />of a "fail safe to close" design fied in this subsection (c) and in <br />shall be provided. Each of the subsections (d), (e) and (f) of this <br />following shall activate automatic section. <br />shut-off: <br /> (1) Connections. <br />[i] Gas detection. <br /> [i] Piping and tubing shall <br />[ii] Manually, from remote be installed in accordance with <br />locations. appropriate nationally recog- <br />710_23 (Pleasanton 5-99) <br />