shown on City Standard Drawing No. BP-3 and provisions must <br /> be made for drainage of the vault in order to prevent <br /> flooding. <br /> <br /> Above ground fire system appurtenances (hydrants, PIV's, <br /> FDC;s) must all have concrete pads of minimum dimension 4'x <br /> 4' x 4" thick. Additionally, above ground double check <br /> detector check valves may be screened with shrubbery on one <br /> side only. <br /> <br /> Ductile iron pipe must be used in the onsite fire system for <br /> one length on each side of the Double Check Detector Check <br /> and also for the last leg of the fire system running to the <br /> sprinkler riser in the building. <br /> <br />3. Miscellaneous Requirements <br /> <br /> a. Where there exists the possibility that vehicles <br /> parking onsite can park parallel to curbs and reduce <br /> the usable drive aisle widths to less than 20 feet, one <br /> of the following must be shown on the plans: <br /> <br /> 1. Curbs must be painted red adjacent to drive <br /> aisles. <br /> <br /> 2. "No Parking" must be painted on the pavement at <br /> frequent locations. <br /> <br /> 3. Signs must be installed at all driveway entrances <br /> specifying that vehicles may park in designated <br /> parking stalls only. <br /> <br /> b. The colors of onsite fire appurtenances must be <br /> contrasting to building or other backdrop colors. If the <br /> color needs to be altered from red for the specific <br /> appurtenance, the new color must be indicated on the plans. <br /> <br /> c. All P.I.V.'s, O.S. & Y. valves or other valves <br /> controlling onsite fire systems are required to be <br /> supervised, per NFPA Pamphlet 13. Conduit runs from valves <br /> to the building shall be included in underground work and <br /> shall be in place prior to paving. <br /> <br />4. When fire protection facilities are to be installed by the <br />developer, such facilities, including all weather surface access <br />roads, shall be installed and made serviceable prior to and <br />during construction. When alternative methods of protection, as <br />approved by the Fire Marshal are provided, the above requirement <br />may be modified or waived. Alternative methods shall be <br /> <br /> 19 <br /> <br /> <br />