Laserfiche WebLink
20.20.027 <br />Table 690.31(C) Correction Factors <br />Temperature Rating of Conductor Temperature <br />Temperature (°C) 60°C (140°F) 75°C (167°F) 90°C (194°F) 105°C (221°F) <br />30 1.00 1.00 1.00 1.00 86 <br />31 - 35 0.91 0.94 0.96 0.97 87 - 95 <br />36 - 40 0.82 0.88 0.91 0.93 96 - 104 <br />41 - 45 0.71 0.82 0.87 0.89 105 - 113 <br />46 - 50 0.58 0.75 0.82 0.86 114 - 122 <br />51 - 55 0.41 0.67 0.76 0.82 123 - 131 <br />56 - 60 - 0.58 0.71 0.77 132 - 140 <br />61 - 70 - 0.33 0.58 0.68 141 - 158 <br />71 - 80 - - 0.41 0.58 159 - 176 <br />690.45 Size of Equipment Groundinc <br />Conductor. <br />Where not protected by the ground- <br />fault protection equipment required <br />by 690.5, the equipment-grounding <br />conductor for photovoltaic source <br />and photovoltaic output circuits shall <br />be sized for 125 percent of the pho- <br />tovoltaic-originated short-circuit <br />currents in that circuit. Where pro- <br />tected by the ground-fault protection <br />equipment required by 690.5, the <br />equipment-grounding conductors for <br />photovoltaic source and photovoltaic <br />output circuits shall be sized in ac- <br />cordance with 250.122. <br />690.47 Grounding Electrode System. <br />(A) Alternating-Current Systems. If <br />installing an ac system, a grounding <br />electrode system shall be provided in <br />accordance with 250.50 through <br />250.60. The grounding electrode <br />conductor shall be installed in accor- <br />dance with 250.64. <br />(B) Direct-Current Systems. If in- <br />stalling a do system, a grounding <br />electrode system shall be provided in <br />accordance with 250.166 for ground- <br />ed systems or 250.169 for unground- <br />ed systems. The grounding electrode <br />conductor shall be installed in accor- <br />dance with 250.64. <br />VI. Marking <br />690.51 Modules. <br />Modules shall be marked with identi- <br />fication of terminals or leads as to <br />polarity, maximum over current <br />(Pleasanton April 2003) '] 10_26 <br />