20.08.049 <br />for leakage at 200 psi for one (1) <br />hour minimum. <br />107.1.5 All sprinkler riser piping <br />shall be either non-ferrous metallic <br />pipe (copper, or brass) or CPVC. All <br />piping above the flow switch shall be <br />protected by sheet rock or plywood. <br />Note: No ferrous (black iron, iron or <br />galvanized) pipe is permitted. <br />Sec. 9.108 Units <br />Metric units of measurement in this <br />standard are in accordance with the <br />modernized metric system known as <br />the International System of Units <br />(SI). Two (2) units (liter and bar), <br />outside of but recognized by SI, are <br />commonly used in international fire <br />protection. <br />108.1 If a valve for measurement as <br />given in this standard is followed by <br />an equivalent value in other units, <br />the first stated is to be regarded as <br />the requirement. A given equivalent <br />value may be approximate. <br />CHAPTER 2 *Water Supply <br />Sec. 9.201 General Provisions <br />Every automatic sprinkler system <br />shall have at least one (1) automatic <br />water supply. When stored water is <br />used as the sole source of supply, the <br />minimum quantity shall equal the <br />water demand rate times ten (10) <br />minutes. <br />Sec. 9.202 *Water Supply Sources <br />The following water supply sources <br />are acceptable: <br />202.1 A connection to a reliable <br />water works system. <br />202.2 *An elevated tank. <br />202.3 A pressure tank installed in <br />accordance with NFPA 13, Standard <br />for the Installation of Sprinkler Sys- <br />tems, and NFPA 22, Standard for <br />Water Tanks for Private Fire Protec- <br />tion. <br />202.4 A stored water source with an <br />automatically operated pump. <br />Sec. 9.203 Multipurpose Piping Sys- <br />tem <br />A piping system serving both fire <br />sprinkler and domestic needs shall be <br />acceptable when: <br />203.1 In common water supply con- <br />nections serving more than one (1) <br />dwelling unit, five (5) gallons per <br />minute (19 L/min) per dwelling unit <br />is added to the sprinkler system <br />demand to determine the size of <br />common piping and the size of the <br />total water supply requirements. <br />Exception: Note Chapter 4 for spe- <br />cific hydraulic calculation require- <br />ments. <br />(Pleasanton April 2000) '700_4 <br />